Generator Wire Size Calculator
What this calculator measures
Estimate conductor area for the entered lagging-PF voltage-drop model using the correct single-phase or balanced three-phase relationship. This is not an ampacity, protection, AWG, or installation approval.
Inputs and units
Use readings and ratings that describe the same equipment, operating interval, and measurement boundary. The sample entries are editable examples; they do not establish the specifications of your generator.
| Input | Example entry or choice |
|---|---|
| Actual simultaneous real-power load (kW) | 100 — enter a documented value |
| Single-phase or three-phase line-to-line voltage (V) | 240 — enter a documented value |
| Circuit type | Choose the matching option — choose the stated basis |
| One-way conductor length (ft) | 100 — enter a documented value |
| Voltage-drop budget for this conductor run (%) | 3 — enter a documented value |
| Lagging load power factor (1 for resistive) | 1 — enter a documented value |
| Operating-temperature copper K (ohm cmil/ft) | 12.9 — enter a documented value |
| Conductor reactance (ohm/ft) | 2.4384e-05 — enter a documented value |
Calculation method
The model uses line current = real W ÷ (V × PF) for single phase, or real W ÷ (√3 × V × PF) for balanced three phase. Longitudinal voltage drop is 2IL(R cosφ + X sinφ) for the two-wire circuit and √3IL(R cosφ + X sinφ) for balanced three phase.
With cosφ = PF and sinφ = √(1 − PF²), solve the resistance term for circular-mil area. Use copper K in ohm cmil/ft and reactance per foot on the same temperature and length basis. If the assumed reactive drop already consumes the entire drop budget, no finite area solves this constant-reactance model and the tool reports a calculation failure.
Worked example
For a 100 kW, 240 V single-phase load at PF 1, 100 ft one-way run, a 3% drop budget, and K = 12.9, the area estimate is approximately 149,305.56 cmil. The two-wire return path is included. The number is an area, not an AWG recommendation or an ampacity approval.
Limitations and checks
Use the conductor manufacturer’s operating-temperature resistance and configuration-specific reactance. The defaults illustrate assumptions. This approximate steady-load voltage-drop calculation does not check ampacity, fault duty, protective coordination, conductor availability, neutral current, mechanical installation, or motor-start voltage dip. A calculated area is not a selected cable.
For a practical decision, keep the original readings, the generator model, the relevant manual or specification, and the assumptions alongside the result. A different load, site condition, rating basis, or unit convention can answer a different question even when the arithmetic is correct.