Generator Wire Size Calculator

Generator Wire Size Calculator

Estimate conductor area for the entered lagging-PF voltage-drop model using the correct single-phase or balanced three-phase relationship. This is not an ampacity, protection, AWG, or installation approval.
Voltage-drop area estimate only:
Support this tool
Buy us a coffee
If this Generator Wire Size Calculator helped you, you can support the site with a small donation. It keeps the tools on the site free and supports ongoing improvements.
Buy us a coffee
Secure donation via Gumroad

What this calculator measures

Estimate conductor area for the entered lagging-PF voltage-drop model using the correct single-phase or balanced three-phase relationship. This is not an ampacity, protection, AWG, or installation approval.

Inputs and units

Use readings and ratings that describe the same equipment, operating interval, and measurement boundary. The sample entries are editable examples; they do not establish the specifications of your generator.

Input Example entry or choice
Actual simultaneous real-power load (kW) 100 — enter a documented value
Single-phase or three-phase line-to-line voltage (V) 240 — enter a documented value
Circuit type Choose the matching option — choose the stated basis
One-way conductor length (ft) 100 — enter a documented value
Voltage-drop budget for this conductor run (%) 3 — enter a documented value
Lagging load power factor (1 for resistive) 1 — enter a documented value
Operating-temperature copper K (ohm cmil/ft) 12.9 — enter a documented value
Conductor reactance (ohm/ft) 2.4384e-05 — enter a documented value

Calculation method

The model uses line current = real W ÷ (V × PF) for single phase, or real W ÷ (√3 × V × PF) for balanced three phase. Longitudinal voltage drop is 2IL(R cosφ + X sinφ) for the two-wire circuit and √3IL(R cosφ + X sinφ) for balanced three phase.

With cosφ = PF and sinφ = √(1 − PF²), solve the resistance term for circular-mil area. Use copper K in ohm cmil/ft and reactance per foot on the same temperature and length basis. If the assumed reactive drop already consumes the entire drop budget, no finite area solves this constant-reactance model and the tool reports a calculation failure.

Worked example

For a 100 kW, 240 V single-phase load at PF 1, 100 ft one-way run, a 3% drop budget, and K = 12.9, the area estimate is approximately 149,305.56 cmil. The two-wire return path is included. The number is an area, not an AWG recommendation or an ampacity approval.

Limitations and checks

Use the conductor manufacturer’s operating-temperature resistance and configuration-specific reactance. The defaults illustrate assumptions. This approximate steady-load voltage-drop calculation does not check ampacity, fault duty, protective coordination, conductor availability, neutral current, mechanical installation, or motor-start voltage dip. A calculated area is not a selected cable.

For a practical decision, keep the original readings, the generator model, the relevant manual or specification, and the assumptions alongside the result. A different load, site condition, rating basis, or unit convention can answer a different question even when the arithmetic is correct.