Generator Fuel Efficiency Calculator

Generator Fuel Efficiency Calculator

Calculate electrical kWh per US gallon from matched average electrical output and liquid-fuel consumption. Measured fuel and load already reflect fuel type and equipment condition, so no category multipliers are applied.
Measured operating-point fuel productivity:
Support this tool
Buy us a coffee
If this Generator Fuel Efficiency Calculator helped you, you can support the site with a small donation. It keeps the tools on the site free and supports ongoing improvements.
Buy us a coffee
Secure donation via Gumroad

What this calculator measures

Calculate electrical kWh per US gallon from matched average electrical output and liquid-fuel consumption. Measured fuel and load already reflect fuel type and equipment condition, so no category multipliers are applied.

Inputs and units

Use readings and ratings that describe the same equipment, operating interval, and measurement boundary. The sample entries are editable examples; they do not establish the specifications of your generator.

Input Example entry or choice
Generator Size (kW) 100 — enter a documented value
Average Load (%) 75 — enter a documented value
Actual liquid-fuel consumption at that load (US gal/h) 7.5 — enter a documented value

Calculation method

Electrical kWh per US gallon = average electrical kW ÷ actual US gallons per hour. Average kW is applicable rated kW multiplied by the corresponding average load fraction. Use output and net fuel consumption from the same period and operating condition.

Worked example

For 100 kW rated output, 75% average loading, and 7.5 US gal/h actually consumed, productivity is 10 kWh/US gal. Equivalently, 600 kWh and 60 US gallons over an eight-hour interval give the same ratio.

Limitations and checks

This is a volume-based productivity measure, not a percentage of fuel energy converted to electricity. Different fuels contain different energy per gallon, so compare energy efficiencies on an appropriate heating-value basis. Natural gas measured in cubic feet or cubic metres should not be relabelled as liquid gallons.

For a practical decision, keep the original readings, the generator model, the relevant manual or specification, and the assumptions alongside the result. A different load, site condition, rating basis, or unit convention can answer a different question even when the arithmetic is correct.